Lots having any of the
following may be determined inappropriate or require special conditions for
graywater irrigation systems:
Mulch basins are formed by digging a
basin deep enough so there is a freefall of water into the basin and so roots
wont clog the 1” to ½ inch barbed plastic tee outlet. The number and size of
mulch basins the landscape will require will vary based on the number of gallons
of graywater expected to discharge daily and the type of soil in the irrigation
field. It is critical to have sufficient volume in the mulch basins to receive
all the graywater discharged without ponding or running off. Deep mulch basins increase soil
percolation, reduce rain runoff, reduce water use, increase soil fertility and
ease stress on water treatment plants and septic tanks. Mulch is organic waste
material including leaves, prunings, straw, pulled weeds and woodchips. It is
recommended to put woody mulch near the bottom of the mulch basin because it is
more durable and permeable.
To get the pressurized graywater to plants, 1”
polyethylene tubing is the preferred distribution plumbing. Polyethylene tubing
is the same material commonly used for drip irrigation, just in a bigger size.
Smaller tubing gives too much resistance. Bigger tubing traps more septic water
and solids. Use the kind with a purple stripe to indicate non—potable water.
All Graywater distribution piping shall be identified with the words “CAUTION:
NONPOTABLE WATER, DO NOT DRINK.” You can run a single or multi-trunk line, with or without
valves or branches. Branches can be 1” or ¾” or ½” drip tubing. It is
recommended that if you have a large volume of graywater and/or low-perk soil,
use two or more valved zones. Be sure to note the location of hidden plumbing
on a drawing or photographs for the operators manual. It is best that the line
slopes downhill continuously to prevent freezing, smells and to ease stress on
the pump. Another option is a U-shaped line with an outlet at the low point to
drain the U, though this may trap water in the line between uses. This is
acceptable, unless freezing temperatures cause the line to freeze. Graywater
can go septic if it sits for more than 24 hours. However, the quantity in even
a long run of 1” pipe is so small that any objectionable smell is only
detectable for the first moment of discharge. In an installation that includes
both some rise and a long horizontal run, the quantity of trapped water is
minimized by sending the pipe up to the maximum height as quickly as possible,
then running the pipe down from there. This way, most of the run drains dry
after each use. This same geometry works to get the water up from a basement
washer to the yard.
1” to ½ inch plastic barbed tee fittings
are recommended for the outlets. Other types of outlets could include ½ in
barbed valves, 3/8” barbed outlets, ¼-3/8” drilled holes. To prevent clogging
use a mulch shield around the outlet. Cut out the sides out of a 1+ gallon
bucket so there is a place for the tubing to run through the center. Cut out
the bottom so it opens like a hinged lid, this will provide a solid shield
covering the outlet release point and easy access for maintenance. Place the
bucket upside down, buried in the mulch basin with the polyethylene tubing
running through the cut out sides of the bucket and the barbed tee outlet
centered inside, preventing the mulch from touching the outlet. The capacity of
all the outlets should be enough that the pump is not strained trying to push
too much water through too small or too few holes. Also too large or too many
holes will result in pressure loss that may leave some outlets dry.
All graywater systems shall be designed to allow the user to direct the flow to either the irrigation field or building sewer. The means of changing the direction of the graywater shall be clearly labeled and readily accessible to the user (CPC Ch.1601A.0 E). A three-way valve is mounted on the wall behind the washer, or where it is easily visible and convenient to turn. It should be solidly secured to the wall using copper pipe brackets so it does not move when the handle is torqued (1” brass valve is ideal. One side of the valve diverts water into the sewer standpipe through a vacuum break, to the graywater system. The graywater destinations should be clearly labeled, e.g. “Sewer” and “Orchard”. NOTE: If you are doing a load with bleach or fabric softener, send the water to the sewer.
If the first outlet is lower than the level of water in the washer, a vacuum breaker is necessary to keep the drain from continuously siphoning water out of the machine as it tries to refill itself. The lose fit of the washing machine drain hose into the standpipe in conventional plumbing creates a vacuum breaker. The vacuum breaker must connect to the main drain line at its high point to be effective. This is typically close to the washer, just outside the house. The drain line shall be hard piped from the washer drain line connection to the irrigation system connection at the exterior of the house. In addition to the air breaker at the highest point of this connection, back flow prevention shall be installed at the connection to the irrigation distribution system.
F) Backflow Prevention
Backflow prevention on the potable water supply
line to the house (i.e., air gap separation, reduced pressure principle
assemble, or double check value) is required if the system meets the definition
of being an “auxiliary water supply”. Systems without a storage tank or pump
may not meet this definition, but backflow prevention is always a good idea.
A temporary hose connection makes tuning the
outlets easier (you won’t have to keep doing load after load of laundry to
check and tune the outlet flows). It is also good for blowing out lint if
needed (be careful to not over-pressurize the system, as the irrigation tubing
connections cannot handle more than about 20psi). Check valves and hose connections may not be required for every system
design. However, if you include these components, the chance of having trouble
with your system is much smaller and the performance and maintenance of the
system will be improved. The hose service connection must be properly
installed with back flow prevention so there is no chance of graywater back
flowing into the freshwater lines. The layers of protection against this are:
1) only connect the hose with washer disconnected; 2) install a swing check
valve; 3) install a backflow prevention device at the hose bib. To tune the
outlets perfectly, check the flow from the washer by timing how long it takes
it to fill a bucket. Then adjust the hose to the same flow. Do not leave the hose connected unless
testing or cleaning the lines.
Laundry
to mulch basin systems use the washing machine pump to distribute the water.
Without stressing the pump you can irrigate any distance downhill, or pump up
to an elevation 2’ below the top of the washer 100’ away (100’ of horizontal 1”
tubing offers the same resistance as 20” of vertical rise). The resistance the
pump has to overcome should ideally be about the same as in a standard installation,
where the hose discharges at the height of the top of the machine. For example,
if a washing machine empties through 100’ of 1” pipe that ends 18” lower than
its lid; the effective resistance is the same as if it discharged 2” above its
lid. To avoid backflow, don’t irrigate at a height above the washer.
I) Soaps and Detergents
Avoid soaps that contain boron, Clorox, salt or sodium (eg. sodium lauryl sulfate) as they can be harmful to your plants.
For more information:
·
California Plumbing Code Chapter 16A Non-potable
Water Reuse Systems: http://www.hcd.ca.gov/codes/shl/Preface_ET_Emergency_Graywater.pdf
·
City of Santa Barbara:
http://www.santabarbaraca.gov/Resident/Water/Water_Conservation/WCSustainableOptions.htm
·
Oasis Designs: http://oasisdesign.net/
(Diagrams, pictures, parts and video on installation process).

(A) Single Family Dwellings and Multi-Family Dwellings. The
graywater discharge for single family and multi-family dwellings shall be
calculated by estimates of graywater use based on water use records,
calculations of locally daily per person interior use, or the following
procedure:
1. The number of occupants of each dwelling unit shall
be calculated as follows:
First bedroom 2
occupants
Each additional bedroom 1 occupant
2. The estimated graywater flows of each occupant shall
be calculated as follows:
Laundry 15
GPD /occupant
3.
The
total number of occupants shall be multiplied by the applicable estimated
graywater discharge as provided above.
Table for Determining Area
of Irrigation/Leaching Required:
|
Table
16A-2 Design Criteria of Six Typical Soils |
||
|
Type of Soil |
Square Feet |
Gallons |
|
|
Minimum square feet of
irrigation/leaching area per 100 gallons of estimated graywater discharge per
day |
Maximum absorption
capacity in gallons per square foot of irrigation/leaching area for a 24 hour
period |
|
Coarse sand or gravel |
20 |
5 |
|
Fine sand |
25 |
4 |
|
Sandy loam |
40 |
2.5 |
|
Sandy clay |
60 |
1.7 |
|
Clay with considerable
sand or gravel |
90 |
1.1 |
|
Clay with small amounts of
sand or gravel |
120 |
0.8 |
|
Table 16A-1 Location of
Graywater System |
||||
|
Minimum Horizontal
Distance Required From: |
Tank |
Irrigation Field |
Disposal Field |
|
|
|
Feet |
Feet |
Feet |
|
|
Building structures (1) |
5 (2) |
2 |
5 |
|
|
Property line adjoining
private property |
5 |
1.5 ft |
5 |
|
|
Water supply wells (3) |
50 |
100 |
100 |
|
|
Streams and lakes (3) |
50 |
100 (4,5) |
100 (4) |
|
|
Sewage pits or cesspools |
5 |
5 |
5 |
|
|
Sewage disposal field |
5 |
4 (6) |
4 (6) |
|
|
Septic tank |
0 |
5 |
5 |
|
|
Onsite domestic water
service line |
5 |
0 |
0) |
|
|
Pressurized pubic water
main |
10 |
10 (7) |
10 (7) |
|
|
(1)
Building structures does not include porches and steps, whether covered or
uncovered, breezeways, roofed porte cocheres, roofed patios, carports,
covered walks, covered driveways and similar structures or appurtenances. |
||||
|
(2)
Underground tanks shall not be located within a 45-degree angle from the
bottom of the foundation, or they shall be designed to address the surcharge
imposed by the structure. The distance may be reduced to six (6) inches for
aboveground tanks when first approved by the Enforcing Agency. |
||||
|
(3) Where
special hazards are involved, the distance required shall be increased as directed
by the Enforcing Agency. |
||||
|
(4) These
minimum clear horizontal distances shall also apply between the irrigation or
disposal field and the ocean mean higher high tide line. |
||||
|
(5) The
minimum horizontal distance may be reduced to 50 feet for irrigation fields
utilizing graywater which has been filtered prior to entering the
distribution piping. |
||||
|
(6) Plus
two (2) feet for each additional foot of depth in excess of one (1) foot
below the bottom of the drain line. |
||||